On 29 April 2025, the long-anticipated update to BS 5839-1 was released. For those involved in fire safety across non-domestic buildings—offices, care homes, schools, hospitals, hotels—this revision marks a significant shift in how fire alarm systems are designed, installed, and maintained. At Optimum Fire and Security Ltd, we believe it’s important not just to follow the rules but to understand why they’ve changed and how they affect real-world environments.
The 2025 update is not just a minor revision. It addresses gaps in previous versions and aims to improve reliability, reduce false alarms, and ensure fire detection systems meet the specific needs of the buildings they serve. One of the key shifts in the new standard is the emphasis on early detection in vulnerable spaces. For example, L4 systems now require detection at the tops of lift shafts, and L2 systems must include sleeping-risk areas, particularly in care homes and accommodation. Smoke detectors are preferred over heat detectors in these settings to provide faster response times.
Manual call points remain a vital part of fire alarm systems, but their placement is now more strategic—only in occupied zones and where they’re easily accessible. There’s also now clear permission for integrating lockdown alarms into fire systems, so long as the tones are distinguishable. This change reflects a growing demand for multipurpose emergency communication within buildings, especially in education and healthcare settings.
For fire alarm panels, there’s a new requirement for a ‘False Alarm Notice’—a visible statement highlighting that the system has an active connection to the fire and rescue service. This is a direct response to ongoing concerns about unnecessary callouts and the importance of avoiding false activations.
Another notable update is how backup power is calculated. The standby battery sizing formula has been revised and clarified, with expanded guidance to ensure systems stay operational during power cuts. Similarly, cable colours must now be red for both fire alarm and low-voltage mains to avoid confusion during installation and servicing.
When it comes to maintenance, the rigid six-monthly servicing requirement has been replaced with a more flexible model. Systems can now be serviced every five to seven months depending on the environment and risk level. This flexibility gives building managers more room to tailor servicing to their operations, while still maintaining safety.
Each service visit must now also include a check and correction of the control panel’s clock. Accurate event logging can make a critical difference in post-incident analysis or insurance investigations. And it’s not just the system being checked—engineers themselves must now commit to continuous professional development (CPD) to ensure they remain competent to carry out inspections and maintenance.
Zone charts, often overlooked, are now under stricter scrutiny. These need to be verified and updated at every visit to ensure emergency responders and building managers can interpret the system layout instantly in an emergency. Outdated or incorrect charts can cause dangerous delays.
There are also changes to how systems should be modified. A brand-new clause addresses extensions and modifications to existing systems, laying out what documentation and certification is required. It ensures that even when systems evolve, their compliance remains intact.
Terminology throughout the standard has been modernised to align with wider regulatory language. For example, ‘care homes’ are now referred to as ‘residential care premises’, and ‘fire service’ has been updated to ‘fire and rescue service’.
So what should building owners, responsible persons, and fire safety professionals do next? The first step is reviewing your current fire alarm system in light of these changes. Are the detectors in the right places? Are your call points accessible and in the correct locations? Is your maintenance contractor up to speed with these new requirements—and are they keeping accurate records?
At Optimum Fire and Security Ltd, we’re already working with clients to bring their systems up to BS 5839-1:2025 standards. From updating zone charts and verifying battery capacity to ensuring all staff are properly trained, we offer comprehensive support to keep your premises compliant and protected.